Expansion of power system causes short-circuit currents (SCC) of networks to exceed the tolerable SCCs of equipment. The utilization of fault current limiter (FCL) in such networks is needed to address this issue. This paper presents a new method for optimal allocation of FCLs to restrain the SCCs under permissible value. In this method, it is suggested to select a line as FCL location where the addition of FCL to this line will have the greatest impact on reducing the SCC of buses which their SCCs exceed the permissible value (known as exceeded buses). Since the optimization algorithms are not capable for optimal allocation of FCL especially in large networks, therefore, the proposed FCL allocation method is presented in the form of a computational process. In this computational process, the candidate lines for FCL location are firstly prioritized by a new index based on the effect of location of FCL on the reduction of SCCs. Then, the FCL size is determined by solving a quadratic equation firstly presented in this paper. The proposed method is implemented on networks with different sizes, and the obtained results show the performance of the proposed method over previous FCL allocation methods.