Search published articles



H. Zayyani, M. Dehghan,
Volume 11, Issue 1 (3-2015)
Abstract

This paper presents a simple and easy implementable Least Mean Square (LMS) type approach for frequency estimation of three phase power system in an unbalanced condition. The proposed LMS type algorithm is based on a second order recursion for the complex voltage derived from Clarke's transformation which is proved in the paper. The proposed algorithm is real adaptive filter with real parameter (not complex) which can be efficiently implemented by DSP. In unbalanced situations, simulation experiments show the advantages and drawbacks of the proposed algorithm in comparison to Complex LMS (CLMS) and Augmented Complex LMS (ACLMS) methods
M. Khoddam, J. Sadeh, P. Pourmohamadiyan,
Volume 13, Issue 1 (3-2017)
Abstract

Circuit Breakers (CBs) are critical components in power system for reliability and protection. To assure their accurate performance, a comprehensive condition assessment is of an imminent importance. Based on dynamic resistance measurement (DRM), this paper discusses a simple yet effective fuzzy approach for evaluating CB’s electrical contacts condition. According to 300 test results obtained from healthy and three defected electrical contacts, the authors describe the special effect of common failures on DRM characteristics and propose seven deterioration indicators. Using these parameters, a fuzzy classifier is suggested to accurately determine contact sets condition. The salient advantage of the proposed model is its capability to recognize the type of contact failure. The feasibility and effectiveness of the proposed scheme has been validated through 40 real life recorded data of some electrical contacts. 



Page 1 from 1     

Creative Commons License
© 2022 by the authors. Licensee IUST, Tehran, Iran. This is an open access journal distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial 4.0 International (CC BY-NC 4.0) license.